I recieved a cut sheet from a gen manufacuter and told him to comply with ANSI C50.13 which will limit the ground fault current Isc SLG to a value less than or equal to the 3 phase fault of the generator. My comment was to increase the zero sequence impedance 3x's the value of my positive sequence.